Electrical connections (IS) with safety barriers
Yellow Connector
Thermocouple
junction box
Thermocouple
2
3
E
SCREEN
+V RD
0V BK
Red Connector
SAFE AREA
1
SCREEN
+V RD
0V BK
1
E
3
2
SCREEN
0V BK
+V RD
2
E
3
1
Blue Connector
Hydrosteel 7000
0V
+V
BK
RD
4-20mA 1
0V
+V
0V
RD
BK
Power
+V
BK
RD
4-20mA 2
Control equipment
Installation
Ion Science Ltd suggest using the following or similar safety barrier or IS isolator for IS approved
applications. The system must be designed by a suitably trained engineer and approved by the local safety
authority.
Power Supply:
Suggested barriers for INLET power supply
* Note
All cable lengths are estimated for Zone 1 IIC installation of the equipment
Using 1 mm
2
C.S.A. conductors S.T.P. cables with capacitance of 250 pF/m, L/R ratio of 25 uH/
conductor resistance at 20 C of 18.4 /Km
Calculation assumes that cables are at 80 C (maximum operating temperature).
Signal Output
Suggested barriers for 4-20mA OUTLET
WARNING! Intrinsically safe (IS) applications
HY7K fuses may not be replaced in the field.
If a fuse is blown the Hydrosteel 7000 will require inspection by Ion Science Ltd or and Ion Science Approved
Service Centre before it is used in an IS application.